Criterion 6.1.2.4 Collector Flow Rate/Distribution

Criteria text:
In multiple collector arrays, the instantaneous flow rate variations between collectors shall not exceed 10% of the array average flow. When an array of collectors is connected by manifolds to form a parallel flow configuration, provision shall be incorporated in the manifold and/or collectors to maintain the proper design flow rate of the heat transfer fluid through each collector.

Comments:

In the majority of systems certified by SRCC, this criteria is not a major concern since most of the installed systems include only 1 or 2 solar collectors.

In the event a large number of solar collectors are installed, a method must be used to maintain proper system (and collector) design flow rates. Two methods are commonly used:

  • Plumbing the collector array in such a manner that allows for proper flow distribution through the individual units.
  • Using balancing valves to manually adjust the flow rate

Figure 1 illustrates the option of using a proper reverse piping strategy and the use of balancing valves. The use of reverse return plumbing in large collector arrays will provide equal flow rate distribution through the collectors.


Figure 1

A conventional manually set balancing valve is shown in Figure 2.


Figure 2

Proceed to the Next Collector Subsystem Guideline

Return to the Collector Subsystem Main Page


Return to SRCC home page

Please address questions and comments regarding this web page to WebMaster