Criterion 6.1.5.2 Control System Override

Criterion text:
The control subsystem shall include such provision for bypass, adjustment or override controls as are required to facilitate installation, startup, operation, shutdown and maintenance of the system. Safety controls shall not have provision for bypass or override. All switches and their function shall be labeled and easily accessible.

Comments:
Installers must use the controller that was specified by the manufacturer for the particular SRCC certified system.

SRCC review has ensured that the control methods have the necessary attributes to meet this standard. For example, differential controllers have on/off settings that can be used during for both system operation as well as service and troubleshooting. Photovoltaic and DC pump combination systems are designed to incorporate an On/Off disconnect switch. This switch must be incorporated in the installed system.

In addition to the system component requirements, informational tags and labels that identify these components and their functions, as well as explain their operational procedures must also be installed.


The SRCC approved manual that explains procedures must also be provided to the client and be available at the system site for reference and future service and troubleshooting.

The differential controller shown in Figure 1 has the capability, as shown in Figure 2 of being manually regulated. The On/Auto/Off switch option in Figure 2 (within blue bold area) provides the installer and system owner the ability to manually select the controller's operational mode.


Figure 1


Figure 2

Another differential controller model also provides the ability to control the unit's operation (Figure 3).


Figure 3

Photovoltaic controlled systems must also have some means to override the control strategy. These systems must also incorporate an On/Off disconnect switch.

The disconnect device shown in Figure 4 below is not an SRCC accepted disconnect switch since the two interconnecting wires have to be separated manually. SRCC requires the use of a basic On/Off switch.


Figure 4

A simple and acceptable On/Off switch is shown in Figure 5. Note that with this type of toggle switch the homeowner does not have to disconnect any wiring connectors. On and Off operation is indicated on the switch and in the event power has to be turned off to the pump, the owner simply toggles the switch to the off position. (Of course, the installer would construct some type of housing to mount the switch.)


Figure 5

Proceed to the Next Control Subsystem Guideline

Return to the Control Subsystem Main Page


Return to SRCC home page

Please address questions and comments regarding this web page to WebMaster