| Criterion
6.1.5.6 Temperature Control
Criterion
text:
The
system shall be equipped with a means for automatically limiting
the temperature of the hot water at the fixtures to a selectable
temperature. The range of selectability shall be at least 10 degrees
C (18 degrees F) and shall include a set point of 50 degrees C
(122 degrees F).
Comments:
The use of a mixing or anti-scald valve will be used
to meet the requirements of this standard.
Use
the valve that has been specified by the manufacturer for the
approved SRCC system that is being installed.
Although the installer will be required to install the specific
valve that has been approved for this system, the installer should
also understand the difference between a common tempering valve
and a true anti-scald valve.
A
tempering valve is meant to be used as a "BTU conserver",
while a true anti-scald valve is recognized as a "safety"
valve. Manufacturers and installers must understand the difference
between these two valves, especially as they relate to safety
and legal ramifications.
Figure
1 illustrates a standard "tempering" valve that is meant
to be used as a "hot water extender" and not as a "safety"
device.

Figure
1
The
manufacturer, as indicated in Figure 2, has made sure to point
out that these tempering valves are not to be used to provide
anti-scald service.

Figure
2
Installers
must also understand that the installation requirements of the
tempering and anti-scald valves very often differ. In most cases,
tempering valves must be installed with a heat trap while the
anti-scald valves do not require this additional plumbing.
A
very common anti-scald valve used in the solar industry is shown
in Figures 3 and 4. Note that the valve does not require a heat
trap and thus can be installed directly to the hot out port. In
addition, note in Figure 3 that the valve can be set to various
temperature levels.

Figure 3

Figure 4
Proceed
to the Next Control Subsystem Guideline
Return
to the Control Subsystem Main Page
|