| Criterion
6.1.3.2 Tank Insulation
Criterion
text:
Except
where required by system design or constrained by safety considerations
tank insulation shall have a minimum of R-2.1 oK-m2/W (R-12 oF-ft2-hr/Btu).
An exterior insulation blanket may be used to satisfy this requirement
Comments:
This criteria is evaluated during the system certification
review.
The
installer must install the tank that is listed in the the manufacturer's
SRCC approved installation manual.
Replacement tanks must meet this requirement as well. In the event
the tank is replaced, the installer must ensure that the R-value
of the replacement tank meets this requirement. (As well as the
gallon capacity.)
In the event the tank does not meet the above stated R-value requirements,
the use of an insulation blanket to bring the R-value up to the
stated requirement is acceptable.
When
installing an insulation blanket, the installer must make sure
that access to the thermostat and heating element covers, listing
label, etc., are maintained. Figure 1 below shows an insulation
blanket retrofit that did not include access to the thermostat
and heating element. This should be avoided for safety and maintenance
purposes.

Figure
1
In the photograph in Figure 2, the installer has made a cut-out
in the insulation blanket for access to the thermostat, heating
element, and reset switch.

Figure 2
Since
heat loss can occur through the top of the tank as well, the tank
in Figure 3 should have been thoroughly insulated.

Figure 3
In
the case in Figure 4, the installer had plenty of insulation but
little in the way of aesthetics!

Figure 4
Some
installers may go too far in their zeal to insulate system components.
Figure 5 shows that that installer not only forgot to include
access to the thermostats, but also included the system pump and
several other components under the insulation blanket! This must
be avoided.

Figure
5
Proceed
to the Next Storage Subsystem Guideline
Return
to the Storage Subsystem Main Page
|