| Criterion
6.1.1.2 Solar Loop Isolation
Criterion
text:
Isolation/bypass
valves must be installed to allow the system owner to bypass the
solar storage tank in the case of a two-tank system, or to shut
off the cold water supply to the solar tank in a one-tank system.
All isolation valves shall be labeled with their normal operating
position indicated.
Comments:
The
installer must install all isolation valves included in the SRCC
approved solar system. The manufacturer's system schematic as
well as the SRCC system schematic indicate the required valves
and their locations.
In
addition, the installer must include a label or tag with each
isolation valve. The label or tag will identify the valves' normal
operating position. The tags and labels are to be provided by
the manufacturer.
Note
that the isolation valves in Figure 1 have been tagged. The tags
provide information on the function of the valves as well as indicate
their normal operating position. Identifying the normal operating
position is especially critical for the homeowner in the event
the valve handle has been readjusted for one reason or another.
In addition, these tag provides valuable (and readily available)
information for future service personnel.

Figure 1
In
many installations, a large number of isolation valves are used.
This can at times be quite confusing for the system owner and
service personnel. Identifying the function of the isolation valves
in Figure 2 can be quite frustrating. (Compare the situation in
Figure 2 with that in Figure 3 where the valves are labeled and
identified.) Labels and tags serve to easily identify the valves
and their function in the overall design of the system.

Figure 2
The
use of accompanying tags and labels (Figures 3 and 4) in a multi-valve
system greatly simplifies the understanding of not only the valves,
but overall system design and operation.

Figure 3

Figure 4
Figure
5 shows that this installer includes tags on a variety of other
valves for quick identification. Note that the system manual is
also exhibited in a prominent location for future reference.

Figure 5
The
valve tag shown in Figure 6 states "Valve used to by-pass
solar heater" but does not indicate the normal operating
position of the valve. Of course, those familiar with ball type
isolation valves understand the relationship between the handle
orientation and the valves operation, but homeowners may not be
as adept at determining this. Instruction as to the position of
the valve handle for normal operation should be included.

Figure 6
The
most common isolation valves used are the ball type valves (Figure
7) due to their ease of use and reliability. In the past, gate
valves (Figure 8) had been used for isolation purposes, but this
is no longer the case. Gate valves were primarily used as cold
service water isolation valves. The use of gate valves as isolation
valves in solar systems is not recommended.

Figure 7

Figure 8
Proceed
to the Next Transport Subsystem Guideline
Return
to the Transport Subsystem Main Page
|