| Criterion
6.1.6.3 Insulation
Criterion
text:
All
interconnecting hot water piping and the final 1.5 meters (5.0
feet) of the cold water supply pipe leading to the system, or
the length of piping which is accessible if less than 1.5 meters,
shall be insulated with R-0.46 oK m2/W (R-2.6 oF-ft2-hr /Btu)
or greater insulation.
All
exterior piping insulation shall be protected from ultraviolet
radiation and moisture damage.
Comments:
Insulation
has a tremendous impact on restricting heat loss in the various
system components. Nowhere is this more critical than in the pipe
insulation since system piping is the transit means for solar
heated liquid.
The
manufacturer's SRCC approved installation manual specifies the
type and thickness of insulation that is to be used. It is critical
that the installer follows the manufacturer's instructions.
Installers
must make sure that all piping is insulated. This includes all
external piping as well as required interior piping. It also includes
proper butting of insulation at termination points, making correct
miter cuts at angle joints, and ensuring that the insulation is
well sealed. Very often, installers overlook small sections of
piping adjacent to various valves - usually in the tank plumbing
area. Although it is quite tedious to cut and attach insulation
to these small areas, it is nevertheless very critical in reducing
system heat loss.
Once
the insulation is installed, it must be protected from ultraviolet
ray degradation with an approved insulation coating.
The
following photographs chronicle good and bad insulation installation
practices.
System
piping in Figures 1 and 2 has been well insulated. Note that the
installer has also secured the insulation with black tape. The
insulation is butted to the tank and cutouts have been made to
accommodate the various valves.

Figure 1

Figure 2
Contrast
the installations shown in Figures 1 and 2 with that shown in
Figure 3. Note that in Figure 3, the installer did not complete
the tank area piping insulation task. These small piping areas
may be tedious to insulate, but are critical in reducing overall
system heat loss.

Figure 3
Note
in Figure 4 how the installer has installed the insulation around
the isolation valves and maintained a tight and well insulated
seal.

Figure 4
Long
pipe runs are very easy to insulated. Just slip the insulation
over the piping and pull it along. Understandably, small sections
of piping - end sections, butted sections, and angle sections
- present their own unique problems and are usually insulation
tasks that are not properly completed. Installers need to take
the time to correctly insulate these areas.
Small
sections of piping (Figure 5) need to be insulated in the same
manner as longer easier to insulate sections. This type of work
does not leave a good impression or instill confidence in the
installation on the part of the the customer.

Figure 5
In
order to provide properly sealed insulation ends, installers should
consider the use of escutcheons at ceiling penetrations (Figure
6). This also greatly affects the aesthetics of the installed
system. Compare Figure 6 with Figure 7.

Figure 6

Figure 7
Special
care must be taken for outdoor pipe insulation. Installers must
use the proper type of insulation for exterior applications. In
addition, the insulation must be protected from ultraviolet ray
degradation.
Figures
8 and 9 reveal what happens when the wrong type of external insulation
is used. In this case, plastic insulation was used. Only rubber
insulation should be used for external applications. Plastic can
be used for internal cold lines but nothing else. Follow the manufacturers
installation instructions and acceptable industry standards and
materials.

Figure 8

Figure 9
Exterior
insulation must be protected from degradation by ultraviolet rays
with some type of coating or jacket. In the case shown in Figure
10, the installer is coating the insulation with an ultraviolet
ray protective paint provided by the manufacturer. SRCC reviews
and approves applicable coatings.

Figure 10
Without
properly protecting the insulation with an ultraviolet ray resistant
coating, the insulation will quickly degrade. The insulation shown
in Figure 11 was coated three months previously with a non-ultraviolet
ray resistant coating and already exhibits deterioration.

Figure 11
Figure
12 shows a well insulated piping bend. Note that the installer
has not only mitered the ends, but has also affixed an insulation
glue compound to keep the two separate sections together.

Figure 12
Figure
13 shows how not to complete an insulation run. The section should
have been mitered (See Figure 12). Not only will this leave the
insulation and piping exposed, but it will also allow water to
drip down the piping between the pipe and insulation.

Figure 13
The
insulation installation in Figure 14 will also lead to future
problems by creating pools where water can accumulate and possibly
seep into the structure.

Figure 14
Installers
should also make sure that insulation is installed on system piping
runs in the attic. (Figure 15)

Figure 15
Proceed
to the Next Transport Subsystem Guideline
Return
to the Transport Subsystem Main Page
|