| Criterion
6.2.5 Freeze Protection
Criterion
text:
1.
Protection from freeze damage under the most severe environmental
conditions that can be expected in actual use shall be provided
for all system components containing heat transfer liquids. The
Supplier of each system shall specify the limit (“Freeze
Tolerance Limit”) to the system’s tolerance of freezing
weather conditions. Systems installed in a location which has
no record of an ambient air temperature below 5oC (41oF) may be
exempted from the requirements of this paragraph except the specification
of a freeze tolerance limit.
2. For systems that rely on manual intervention for freeze protection,
the Supplier shall specify the system’s freeze tolerance
limit based on exposure for 18 hours to a constant atmospheric
temperature. SRCC will evaluate the system design to determine
the reasonableness of the specified limit.
3. For solar systems where the collector fluid is water, a minimum
of two freeze protection mechanisms shall be provided on each
system. Manual intervention (draining, changing valve positions,
etc.) is suitable as one mechanism. At least one freeze protection
mechanism, in addition to manual intervention, shall be designed
to protect components from freeze damage, even in the event of
power failure. The thermal mass of a system can be considered
to be a limited form of freeze protection.
4. A system in which components and/or piping are subject to damage
by freezing shall have the proper fittings, pipe slope and collector
design to allow for manual gravity draining and air filling of
the affected components and piping. Pipe slope for gravity draining
shall have a minimum 2 cm vertical drop for each meter of horizontal
length (1/4 inch per foot). This also applies to any header pipes
or absorber plate riser tubes internal to the collector.
5. At the time of installation, a conspicuously placed label explaining
how the system is protected from freezing and what actions the
homeowner should take shall be attached to the system. For systems
which rely on manual intervention for freeze protection, this
label shall indicate the minimum ambient temperature conditions
(Freeze Tolerance Limit) below which owner action is recommended
and the procedure to be followed.
Comments:
The SRCC review and certification process has ensured
that SRCC certified systems are designed to meet this criterion's
freeze protection requirements.
Installers
must install the SRCC certified system provided by the manufacturer.
The manufacturer and installer must understand what types of systems
are valid for use in specific climatic areas.
Each of the above criterion items will be discussed separately
below.
Item
1
The manufacturer has specified the freeze limits of the solar
system and SRCC has reviewed and certified the system for such.
Therefore, logically, the manufacturer would only provide installers
solar systems that are suitable for the installers' specific climatic
conditions.
The
installer in turn must only install those systems that the manufacturer
has determined are suitable for their locations. The manufacturer
and installer must coordinate the type of system that is procured.
Item
2
SRCC has evaluated the freeze tolerance limit for particular SRCC
certified systems.
The
installer and manufacturer need to understand the climatic conditions
where the certified SRCC systems are being installed. The manufacturer
would in turn provide the most suitable system for that geographical
area.
Item
3
This requirement stipulates that when the collector fluid is water,
a minimum of 2 freeze protection mechanisms shall be provided
with the system. The SRCC review process ensures that this is
the case. Installers should therefore install the system by following
the manufacturer's SRCC approved installation methods and using
the manufacturer specified design and components.
Since
manual intervention (draining) is one option, the system must
be installed in a manner that not only allows proper draining
but also includes the valves used in this procedure.
Item
4
The installer must install the certified system in accordance
with the manufacturer's SRCC approved installation manual and
procedures.
The
installer must ensure that for systems in which components or
piping are subject to freeze damage, proper collector and piping
slope is achieved to allow manual gravity draining. A minimum
of 1/4 inch per foot is required for both piping and collector.
Pipe
slope is also discussed in Criterion 6.5.15 Pitch or Angle of
Piping Installation.
Item
5
A freeze information label, provided by the manufacturer, and
affixed to the system by the installer is required. This label
describes the basic freeze prevention methods and what actions
the owner needs to take.
Figure
1 indicates the information that should be provided in the SRCC
freeze information labels.

Figure 1
Installers
must use the SRCC certified system that has been approved for
their particular location and follow the manufacturer's SRCC approved
installation procedures (and schematic).
Proceed
to the Next Transport Subsystem Guideline
Return
to the Transport Subsystem Main Page
|